MK-Copper 

545,25 EUR / 100 kg
status: 27.07.2016

 

Operating Data

Operating Data for collective Tracks in Cu complies DIN 43671 and Aluminum complies DIN 43670

One track per conduct, AC at 60 Hz, environmental temperature 35 °C increasing by 30 °C. Two parallel utilized collective tracks with small distance to each other cannot collectively calculated for a double current but only 1.7 times the current for one track.
Please, see also DIN 43670 and DIN 43671.

Operating Data for Cu Braid and Cu braid Bands

Starting environmental temperature at 35 °C increasing to temperature max. at 70 °C

Nenn-querschnitt in Quadratmillimeter Belastung in Ampere
0.1 5
0.14 6
0.2 7
0.25 9
0.35 10
0.5 12.5
0.75 15
1 18
1.5 21
2.5 30
4 40
5.25 44
Cross Section in Quadratmillimeter Current in Ampere
6 55
8 70
10 85
16 120
25 150
35 195
50 250
70 300
95 360
120 420
150 480
185 570
Nenn-querschnitt in Quadratmillimeter Belastung in Ampere
240 670
300 780
400 950
500 1100
625 1300
800 1500
1000 1800
1500 2200
2000 2400
3000 3000